GREE, 20 SEER, Inverter Heat Pump, 30KBTU, 208/1/60, ODU, GWH30QFXH-D3DNB2A/O

SUBMITTAL DATA 20 SEER: GWH30QFXH-D3DNB2A/O GREE single-zone mini-split systems provide efficient heating and cooling for targeted areas...
Vendor: Gree
SKU: GWH30QFXH-D3DNB2A/O
Availability: Out Of Stock
Please login to see the price
Please login to see the price
Please hurry! Only 0 left in stock
10 customers are viewing this product

SUBMITTAL DATA 20 SEER: GWH30QFXH-D3DNB2A/O

GREE single-zone mini-split systems provide efficient heating and cooling for targeted areas within residential or commercial environments. These single-zone heat pumps and air conditioners offer customizable temperature control wherever they are installed, making them ideal for use in standalone homes or businesses, as well as in spaces that are not connected to an existing HVAC system, such as sunrooms.

Energy Efficiency

  • In Canada, the cold climate demands significant energy consumption for space heating. On average, space heating comprises a remarkable 61% of energy usage in Canadian homes and 56% in commercial and institutional settings. By implementing energy-efficient heating solutions, we can actively combat global warming while reducing energy consumption in both residential and commercial spaces.
  • Our product incorporates the eco-friendly R410A refrigerant, promoting environmentally conscious cooling practices. R410A is a chlorine-free refrigerant known for its exceptional energy efficiency and minimal impact on the ozone layer.

Home Comfort

  • Whisper-quiet operation: Enjoy a peaceful and serene home environment with our quiet design, ensuring minimal noise disruption during operation.
  • Our home comfort system boasts a wide operating range specifically designed for heating. From chilly autumn evenings to freezing winter temperatures, our system ensures optimal warmth and comfort throughout the colder months. With its ability to efficiently heat your home across a wide range of temperatures, you can rely on consistent and reliable performance, keeping you cozy regardless of the outside conditions. Say goodbye to cold spots and welcome a comfortably heated home with our wide operating range feature for heating.

Convenient Operation

  • Complete GREE Kit Installation: Opt for a hassle-free installation by selecting our comprehensive GREE kit, which includes all the necessary components for a seamless setup.
  • Retrofit with Third-Party Indoor Unit or Furnace: If you already have a third-party indoor unit or a furnace combined with a cased coil, you have the flexibility to retrofit our system, reducing both labor and equipment costs.

Reliable Function

  • Low Temperature Two-stage Compressor: Our heat pumps are equipped with a low temperature two-stage compressor, enabling efficient heating even in extreme climates with temperatures as low as -30.
  • Full 3-DC Inverter: With the full 3-DC inverter technology, our heat pumps offer precise and intelligent temperature control, ensuring optimal heating and cooling performance.
  • Bridge-free Digital PFC Control: The bridge-free digital PFC (Power Factor Correction) control further enhances the efficiency and stability of our heat pumps, delivering consistent and reliable performance.
  • The heat pumps feature a cutting-edge two-stage variable speed compressor, delivering exceptional performance and efficiency.
  • Our system offers a convenient retrofit capability, allowing for easy upgrades to your existing heating and cooling setup.

Warranty Coverage

Airtek/Gress proudly backs all their models with a robust manufacturer's warranty. This comprehensive warranty spans an impressive 10 years, safeguarding your investment. Rest assured, any warranty claims you may have will be efficiently handled by Airtek/Gress's, guaranteeing top-tier customer support and satisfaction. The 10-year warranty encompasses the compressor, while other parts enjoy coverage for 5 years. With this warranty, you can trust in the long-term protection of your purchase, ensuring you receive the utmost quality.

SPECIFICATIONS GWH30QFXH-D3DNB2A/O
System Type HEAT PUMP
SYSTEM PERFORMANCE
Cooling 7780 - 35500 Btu/h
Capacity @95'F 30000 Btu/h
Heating 9100 - 36850 Btu/h
Capacity @5¬¨àûF
Capacity @17¬¨àûF 17500 Btu/h
Capacity @47¬¨àûF 30000 W
SEER2 20
EER2 11.3
HSPF/HSPF2 8.5
COP @5¬¨àûF
COP @47¬¨àûF 3.4
Cooling Temperature Range -4 - 115 'F
Heating Temperature Range -4 - 115 'F
Refrigerant Type R410A
INDOOR UNIT GWH30QFXH-D3DNB2A/1
Air flow (Min-Max) 471-912 CFM
Sound Pressure Level (Min - Max) 37-56 dB(A)
Dehumidification 7.4 pt/hr
External Dimensions (WxHxD) 53-3/16 x 12-13/16 x 9-15/16 in
Package Dimension (W x H x D) 56-3/416-5/8 x 14-1/2 in
Net Weight 44.1 lbs
Gross Weight 54 lbs
OUTDOOR UNIT GWH30QFXH-D3DNB2A/O
Compressor Type GREE G-10/2-STAGE INVERTER
Sound Pressure Level 62 dB(A)
External Dimensions (W x H x D) 39-3/8 x 29-3/8 x 16-13/16 in
Package Dimension (W x H x D) 42-9/16 x 31-15/16 x 19-1/16 in
Net Weight 113.6 lbs
Gross Weight 124.6 lbs
REFRIGERANT PIPING
Refrigerant Charge - R410A 74.1 OZ
Additional Charge 0.5 oz/ft
Line Set Size (Liquid - Gas) - Flared Connections 1/4-5/8 in
Pre-Charge Length 25 ft
Pipe Length (Min - Max) 10 - 82 ft
Max. Pipe Elevation 33 ft
ELECTRICAL
Power Supply 208-230V/1Ph /60Hz
Voltage Range (Min - Max) 187 - 253 VAC
Rated Current - Cooling 20 A
Rated Current - Heating 18 A
MCA 20 A
MOCP 30 A
Suggested Breaker Size 20 A
Main Power Wire Size Per Local Code AWG
Interconnecting Wire Size 14/4 AWG

Gree Error Codes

  • E1 - Compressor high pressure protection
  • E3 - Compressor low pressure protection
  • E4 - Compressor air discharge high-temperature protection
  • F2 - Condenser temperature sensor error
  • F3 - Outdoor ambient temperature sensor error
  • F4 - Discharge temperature sensor error
  • F6 - ODU tube temperature sensor error
  • EE - ODU memory chip error
  • H4 - Overload
  • H5 - IPM protection
  • H6 - DC fan error
  • H7 - Driver out-of-step protection
  • HC - Pfc protection
  • Lc - Startup failure
  • P0 - Driver reset protection
  • P5 - Over-current protection
  • P6 - Master control and driver communication error
  • P7 - Driver module sensor error
  • P8 - Driver module high temperature protection
  • PA - AC current protection
  • Pc - Driver current error
  • PL - Bus low-voltage protection
  • PH - Bus high-voltage protection
  • PU - Charge loop error
  • ee - Drive memory chip error
  • e1 - High pressure sensor error
  • C4 - ODU jumper cap error